This 20-foot container-type energy storage system features a fully integrated design, combining the battery pack, battery management system, energy management system, thermal control system, and fire protection system into a pre-tested, all-in-one unit for rapid deployment. The system provides high power output and flexible capacity configuration to meet the demanding application requirements of power generation, grid, and commercial and industrial sectors. Its unique hybrid cooling technology and string-type inverter design effectively enhance system efficiency and available capacity, while the cluster-level control system allows for easy expansion, catering to diverse energy needs.
Model | EL2980-2H | EL2600 | EL2230 | EL1860 | EL1490 | EL2980-4H |
AC Side | ||||||
Rated Output Power | 186 kW*8 | 186 kW*7 | 186 kW*6 | 186 kW*5 | 186 kW*4 | 186 kW*4 |
Rated Voltage |
690 V | |||||
AC side connection | 3W+PE | |||||
Voltage Range | 587V~759 V | |||||
Rated Output Current | 1245 A | 1089 A | 933 A | 778 A | 622 A | 622 A |
Rated Frequency | 50/60 Hz | |||||
Total Harmonic Distortion (THDi) | ≤3% | |||||
Power Factor | -1 ~ +1 | |||||
DC Side | ||||||
Battery Type | LFP , 3.2 V / 280 Ah | |||||
Battery PACK Configuration | 1P*52S | |||||
Battery Capacity | 2981 kWh ( 46.59 kWh * 8 * 8 ) | 2609 kWh ( 46.59 kWh * 8 * 7 ) | 2236 kWh ( 46.59 kWh * 8 * 6 ) | 1863 kWh ( 46.59 kWh * 8 *5 ) | 1490 kWh ( 46.59 kWh * 8 * 4 ) | 2981 kWh ( 46.59 kWh * 8 * 8 ) |
Rated Battery Voltage / Voltage Range | 1331.2 V / 1164.8...1497.6 V | |||||
Max. Charging/ Discharging Current | 140 A*8 | 140 A*7 | 140 A*6 | 140 A*5 | 140 A*4 | 140 A*4 |
Max. Charging/ Discharging Power | 1456kW /1528 kW | 1274 kW /1337 kW | 1092 kW / 1146 kW | 910 kW / 955 kW | 728 kW / 764 kW | 728 kW / 764 kW |
General Data | ||||||
Dimensions (W*D*H) | 6058*2438*2896 mm | |||||
Weight | ~ 32 t | ~ 28.4 t | ~ 24.8 t | ~ 21.2 t | ~ 17.6 t | ~ 32 t |
Operating Temperature Range | -20°C~+60°C (derating @ > 50°C) | |||||
Relative Humidity | 0~95%RH (Non-condensing) | |||||
Altitude | ≤ 2000 m | |||||
Cooling | Smart Air Cooling (PCS) Liquid Cooling (Battery) | |||||
Noise | < 75 dB | |||||
Ingress Protection | IP55 | |||||
Firefighting | Smoke Detector, Heat Detector, Alarm Sounder, Aersol, Sprinkler, Flammable Gas Detector, Vent Plate | |||||
Communication | RS485 / CAN / LAN | |||||
Installation | Floor-standing | |||||
Standard | IEC62619, IEC63056, IEC62477, IEC61000, UN38.3, EN50549-1, EN50549-2, EN50549-10 | |||||